Modbus
®
Mapping Assignments for Micro Motion
®
Transmitters 27
Modbus Mapping Assignments continued
Polling control option codes (holding register 40302 or 41144)
0 Do not poll
ÖÖ
1 Poll transmitter: HART primary
ÖÖ
2 Poll transmitter: HART secondary
ÖÖ
Polling type option codes (holding register 41147)
0 None
1 Pressure compensation only
ÖÖ
3 API only (temperature)
ÖÖ
6 Pressure compensation and API (temperature)
ÖÖ
Polled variable codes (holding registers 41145-41146)
53 Externally read pressure
ÖÖ
55 Externally read temperature
ÖÖ
Output type codes (holding registers 41166-41168)
0 Milliamp (primary) output
ÖÖ
1 Frequency output
ÖÖ
2 Digital communications
3
ÖÖ
3 Milliamp (secondary) output
4
Ö
4 Discrete output
ÖÖ
5 Discrete input
5
Ö
Discrete input assignment codes (holding register 41176)
5
0 None
Ö
1 Start sensor zero
Ö
2 Reset mass total
Ö
3 Reset volume total
Ö
4 Reset corrected volume total
Ö
Discrete output assignment codes (holding registers 41151 and 41153)
10 Event 1 active
ÖÖ
11 Event 2 active
ÖÖ
100 Event 1 or event 2 active
ÖÖ
101 Flow switch indication
ÖÖ
102 Forward/reverse indication
ÖÖ
103 Calibration in progress
ÖÖ
104 Fault condition indication
ÖÖ
Power source codes (holding registers 41174-41175)
0 External
ÖÖ
1 Internal
ÖÖ
Burst command option codes (holding register 41165)
1 Read primary variable
ÖÖ
2 Read PV current and percent of range
ÖÖ
3 Read dynamic variables and PV current
ÖÖ
33 Read transmitter variables
ÖÖ
Table 2-8. Integer codes continued
MVDSolo
Series
1000
Series
2000 RFT9739
Vedere la pagina 32