Reference Manual
00809-0600-4026, Rev BA
December 2011
4-7
Rosemount Process Radar
Figure 4-6. Surface threshold is
too high
Figure 4-7. Surface threshold is
too low
Recommended Actions
Adjust ATC threshold to detect the actual surface peak.
Alternatively adjust Upper Null Zone.
Interface pulse not detected
3.0 5.0
The Surface Threshold is
above the Surface peak
Surface Threshold=
Amplitude Threshold
Curve (ATC)
Reference Threshold
Amplitude, mV
Distance, m
3.0 5.0
Actual surface
Disturbing
echo
misinterpreted
as product
surface
Amplitude, mV
Distance, m
Reference Threshold
Surface Threshold=
Amplitude Threshold
Curve (ATC)