Reference Manual
00809-0600-4026, Rev BA
December 2011
2-13
Rosemount Process Radar
Click Next and the following window appears (Geometry).
7. Enter Tank Height, the distance from the Upper Reference Point to the
Lower Reference Point (which is the tank bottom in the screenshot
above), making sure it is as accurate as possible. See Configuration in
the Rosemount 5300 Series Reference Manual (Document No.
00809-0100-4530) for details.
Set Mounting Type. Set Diameter if Mounting Type is Nozzle or
Pipe/Chamber. Set Nozzle Height if Mounting Type is Nozzle.
Fast Key Sequence [2, 1, 3]
F
OUNDATION fieldbus parameters:
TRANSDUCER 1100>GEOM_TANK_HEIGHT
TRANSDUCER 1100>MOUNTING_TYPE
TRANSDUCER 1100>PIPE_DIAMETER
TRANSDUCER 1100>NOZZLE_HEIGHT
Vedere la pagina 22