Bulletin 71.4:LR128
10
Capacity Information
Note
Flow capacities are laboratory
veried; therefore, regulators may
be sized for 100% ow published
capacities. It is not necessary to reduce
published capacities.
The capacity information on the following pages is
based on percentages of pressure build-up over set
pressure (10%, 20%, 30% or 40%).
Table 12 shows C
v
values at different percentages of
pressure build-up over set pressure and selected
set pressures.
Table13showstheliquidowcapacitiesofthe
Type LR128 relief valve or backpressure regulator
at different percentages of pressure build-up over
set pressure and selected set pressure. Flows are in
gallonsperminute(GPM)andlitersperminute(L/min)
of water.
CRITERIA
17E68 NITRILE (NBR)
(STANDARD)
17E97 NITRILE (NBR) 17E88 FLUOROCARBON (FKM)
Liquid Temperature -20 to 150°F / -29 to 66°C 0 to 150°F / -18 to 66°C 0 to 250°F / -18 to 121°C
(1)
GeneralApplications
Best for low pressure differential
and cold temperature
service applications.
Best for abrasive or
erosive service applications.
Best for high
temperature applications.
HeavyParticleErosion Fair Excellent Good
1. Fluorocarbon (FKM) is limited to 200°F / 93°C in hot water.
Table 10. Diaphragm Material Selection Information
BODY SIZE MAIN VALVE BODY, lbs / kg
In. DN NPT or SWE CL150 RF CL300 RF CL600 RF
1 25 22 / 10 24 / 11 28 / 13 32 / 15
2 50 51 / 23 54 / 24 58 / 26 65 /29
3 80 103 / 47 107 / 49 110 / 50 123 / 56
4 100 139 / 63 145 / 66 159 / 72 192 / 87
Table 11. Approximate Weights Including Type MR98H Pilot and Restrictor
RESTRICTOR SETTING C
v
C
1
Setting 2 0.03
35
Setting 4 0.07
Setting 6 0.14
Setting 8 0.17
Table 9. Type 112 Restrictor Flow Coefcients
Table 8. Flow and Sizing Coefcients for Type MR98H Pilot
BODY SIZE
WIDE-OPEN COEFFICIENT
C
1
K
m
IEC SIZING COEFFICIENTS
X
T
F
D
F
L
C
v
C
g
1/2 in. / DN 15 3.4 120 35.3 0.88 0.787 0.78 0.94
K
m
= F
L
2