tions can be a powerful tool for diagnosing system
problems.
The fault history and the record of run cycles
maintained in the Intelligent Store™ Discus® memory
cannot be re-set. If a compressor is replaced, the E2
notebook feature (see section 5.7 of this manual)
should be used to maintain a record of faults at the
time of replacement (if the Intelligent Store™ Discus®
front box is transferred to the new compressor). This
record will make it easier to determine which faults
belong to the new compressor, and which ones
belong to the old compressor.
1.2
Features
1.2.1 Compressor Protection
Compressor protection may be in the form of a TRIP,
where the compressor will be shut off until the fault
condition no longer exists, or a LOCKOUT. A LOCK-
OUT is a condition whereby the compressor will
remain off until the fault condition no longer exists
AND the manual reset button is pushed. Oil pressure
and discharge temperature lockouts may also be
reset remotely through UltraSite™ if this password
protected feature is enabled. Refer to sections 4.0
and 5.0 of this bulletin for more detailed information
regarding compressor operation and interpretation of
status codes.
The following compressor protection features are
provided on all Intelligent Store™ Discus® compres-
sors:
• High discharge pressure
• Low suction pressure
• Discharge temperature
• Line-break motor protection (2D/3D)
• Motor temperature protection (Intelligent
Store™ Discus® replaces the solid-state
module used on 4D compressors)
• Low voltage
• Power interrupt motor protection
• Welded contactor protection
• Loss of phase motor protection
• Low oil pressure (Intelligent Store™ Discus®
replaces the Copeland® brand Sentronic+™
oil pressure protection module)
The following options are available on Intelligent
Store™ Discus® compressors:
• Liquid injection for discharge temperature
control (Intelligent Store™ Discus® replaces
the Demand Cooling module on HCFC-22 low
temp models)
• Crank case heater
• Capacity modulation
1.2.2 Remote Reset
Oil pressure lockout and discharge temperature
lockout may be reset through the E2 or remotely
through UltraSite™. The oil pressure lockout reset
feature is password protected.
Service contractor and end user policies need to be
considered when deciding whether to enable or
disable the oil pressure remote reset feature. The
default condition is to “disable” this feature.
Refer to section 3.8 for enabling or disabling remote
reset.
1.2.3 Failsafe Operation
The “Failsafe” mode may be configured (through the
E2 during commissioning) to turn the compressor on
or off in the event of a communications failure. The
Intelligent Store™ Discus® will revert to the failsafe
setting (to either RUN or to remain OFF) when
communications are lost for 5 or more minutes.
The default setting for all Intelligent Store™ Discus®
compressors leaving the Emerson Climate
Technologies, Inc. factory is “ON”. If the rack has not
been commissioned, system charging may be accom-
plished by supplying pilot circuit power to the
Intelligent Store™ Discus® compressor with the E2
OFF. After 5 minutes the Intelligent Store™ Discus®
will send a run command to the contactors.
Compressors with power to the contactors will then
RUN with fully enabled protection features (e.g.,
suction and discharge pressure, discharge tempera-
ture, motor protection).
During the commissioning process decisions should
be made regarding which compressors should run
and which ones should not when communication has
been lost.
1.2.4 Welded Contactor Protection
Voltage is sensed at the motor terminals of the
Intelligent Store™ Discus® compressor. If voltage is
present after the contactor has been signaled to
“open”, the module will send a welded contactor alarm
to the E2. The E2 then issues a run command to the
module to load the contactor, bringing all three legs of
the power supply back on line. This prevents a single-
phase motor burn. The compressor will run continu-
ously until the unit is manually shut down. Safety
devices (pressure switches and motor protection) will
override this feature.
This is not to be confused with single-phase protec-
tion at start-up or while running. In that case, the
contactor will be instructed to “open”, shutting down
the compressor.