1. Overview of Emerson Climate
Technologies Intelligent Store™
Discus® Compressor
The Intelligent Store™ Discus® product line is now
available on 2D, 3D and 4D compressors and
integrates a number of important sensing and
compressor protection functions. This product
provides a Network Communications Interface (NCI)
for on/off control of the compressor, capacity modula-
tion and for communication of compressor status to
the Computer Process Controls™ (CPC) E2 rack
controller. Protection against low oil pressure, exces-
sive discharge temperature, high discharge pressure
and low suction pressure is standard on every
Intelligent Store™ Discus® compressor. A prominent
7-segment display on the front of the Intelligent
Store™ Discus® compressor indicates at a glance the
operational status of the compressor.
Note: Throughout this manual the term “module”
refers to the electronic control box of the Intelligent
Store™ Discus® compressor.
1.1 Functionality
1.1.1 Diagnostics
The Intelligent Store™ Discus® compressor continu-
ally displays a code indicating the compressor status.
Normal conditions such as “On”, “Off”, “Injecting
Liquid” and “Low Suction Pressure” are displayed with
a steady code. Indications of fault conditions (e.g.,
low oil pressure, high discharge pressure, etc.) are
displayed with a flashing code. The status codes in
figure 1.0 are discussed thoroughly in this manual,
along with troubleshooting charts to help diagnose
root causes.
These status codes may also be viewed directly on
the E2 controller window, remotely through
UltraSite™ or other remote monitoring software avail-
able from CPC (Computer Process Controls™).
Figure 1.0 Intelligent Store Discus Status Code Table
1.1.2 Communications
Communication between the rack controller and each
Intelligent Store™ Discus® is through an NCI485 net-
work with an RS485 electrical interface and jumper
termination. The two-wire communication cable is
daisy-chained from one compressor to the next on
each rack.
Compressor operations such as on/off control,
modulation operation, transmission of compressor
status and run proofing are all accomplished through
the communication network. Password protected
remote reset of certain compressor lockouts may also
be done through the communication network if this
functionality has been enabled in the controller.
The E2 may be configured to send alarms for
different levels of compressor faults, such as for
“lockouts” or for “trips”.
The “Failsafe” mode may be configured to turn the
compressor on or off in the event of a communica-
tions failure. This configuration is accomplished
through the E2 control panel (reference section 3.7).
1.1.3 Fault History
The most recent compressor trips and lockouts may
be observed through the E2 control panel, UltraSite™
or other remote monitoring software. A time-date
stamp on each fault enables correlation of compres-
sor faults to system events. A running tally of lockouts
and run cycles is accessible through the E2.
Graphing of compressor history (such as run cycles,
injection cycles or system conditions) and fault condi-
AE8-1337 R1