MODBUS Termination Blocks Standard Values • 23
18 Standard Values
Label Description Range Default Level
Fty Kind of gas R22, 134, 404, 407, 410, 507, CO2 404 Pr2
PEo Probe error opening percentage 0 to 100% 50 Pr2
PEd Probe error delay before stopping regula-
tion
0 to 239 sec - On On Pr2
tEU Type of stepper motor uP – bP bP Pr2
tEP Automatic valve configuration 0 to 10 1 Pr2
LSt Minimum number of steps 0 – Ust See tEP Pr2
Ust Maximum number of steps LSt – 800 * 10 See tEP Pr2
Sr Step rate 10 to 600 step/s See tEP Pr2
CPP Current per phase (only bipolar valves) 0 to 100 * 10mA See tEP Pr2
CHd Holding current per phase (only bipolar
valves)
0 to 100 * 10mA See tEP Pr2
oPE Start opening percentage 0 to 100% 85 Pr2
SFd Start function duration 0.0 to 42.0 min: tens of seconds 1.3 Pr2
Sti Stop regulation interval 0.0 to 24.0 hr: tens of minutes 0 Pr2
Std Stop duration 0 to 60 min 0 Pr2
MnF Maximum opening percentage 0 to 100% 100 Pr2
FOP Forced opening time-out 0 to 100% - not used not
used
Pr2
PI PARAMETERS (For trained staff use only)
Pb Proportional band 0.1 to 50.0°C/ 1 to 90°F 10.0 Pr2
rS Band offset -12.0 to 12.0°C/ -21 to 21°F 0.0 Pr2
inC Integration time 0 to 255 sec 120 Pr2
PROBE PARAMETERS
tPP Type of pressure transducer 420 - 5V- LAn 420 Pr2
LPP Enable pressure probe sending in LAN n to YnPr2
PA4 Probe value at 4mA or at 0V
(related to PrM parameter)
-1.0 bar/ -14 PSI -0.5 Pr2
P20 Probe value at 20mA or at 5V
(related to PrM parameter)
PA4 to 50.0 bar/ 725 PSI 11.0 Pr2
OPr Pressure probe calibration -12.0 to 12.0 bar/ -174 to 174 psi 0 Pr2
ttE Type of temperature probe PtM to ntC PtM Pr2
otE Temperature probe calibration -12.0 to 12.0°C/ -21 to 21°F 0 Pr2
DIGITAL INPUTS
i1P Free of voltage digital input polarity
CL – OP CL Pr2
d1d Digital input 1 (free of voltage) activation
delay
0 to 255 min 0 Pr2
Table 18-1 - XEV22D Standard Parameter Values