14 • XEV22D I&O Manual 026-1206 Rev 0 09-FEB-2011
11 Electrical
Connections
The controller comes with a screw terminal block
to connect cables with a cross section up to 2.5 mm
2
.
Heat-resistant cables have to be used. Before connect-
ing the cables, verify that the power supply complies
with the controller’s requirements. Separate the probe
cables from the power supply cables, from the outputs
and the power connections. Do not exceed the maxi-
mum current allowed on each relay, in case of heavier
loads, use a suitable external relay.
11.1.Probes
The recommended temperature probe placement is
illustrated in Figure 11-1, between 0 and 180 degrees
of inclination with respect to the horizontal pipe sec-
tion. For suction pressure probes, there is no particu-
lar recommendation.
12 RS485 Serial Line
All models can be connected to the monitoring and
supervising system XWEB3000. If Mod = StD, the
standard MODBUS-RTU protocol is used; if Mod =
AdU, the custom XWEB library is required
. This last
configuration makes it possible to use the same serial
address of the thermostat that gives the cooling re-
quest to XEV. In this way, it is possible to reduce the
number of addresses used.
Figure 11-1 - Recommended Temperature Probe Placement