Emerson DLC3010 Manuale delle Istruzioni Pagina 14

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 116
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 13
Instruction Manual
D102748X012
Installation
October 2014
14
Figure 2‐1. Installation Flowchart
START HERE
Factory mounted
on 249 sensor?
Use Setup Wizard
to enter sensor
data and
calibration
condition
Check Alarm
Jumper Position
Mount and Wire
Digital level
Controller
Power
Digital level
Controller
No
Yes
Install heat
insulator
assembly
High
temperature
application?
Yes
No
Set Level Offset
to Zero
Calibrate
sensor
Wire
Digital Level
Controller
Power
Digital Level
Controller
Enter Tag, Messages,
Date, and check or set
target application data
Density
Measurement?
Set
Range Values
Using
Temperature
Correction?
Set
Temperature
Units
Setup specific
gravity tables
Set
Specific Gravity
Yes
No
Yes
No
Using RTD?
Yes
Setup and
Calibrate RTD
Enter Process
Temperature
No
1
1
DONE
Disable Writes
NOTE:
1 IF USING RTD FOR TEMPERATURE CORRECTION,
ALSO WIRE RTD TO DIGITAL LEVEL CONTROLLER
2 DISABLING WRITES IS EFFECTIVE ONLY IF THE DLC3010 REMAINS
POWERED‐UP
2
Vedere la pagina 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 115 116

Commenti su questo manuale

Nessun commento