Installation
Input Power Connections
Epsilon Only
Power must be "Off" for a minimum of 6 minutes for the Epsilon drive before unplugging
the power connection, to ensure the bus voltage has bled down to a safe level (below 50
VDC).
Figure 11: Epsilon AC Power Wiring Diagram
Do not connect or disconnect AC power by inserting or removing the AC power
connector. Using the connector in this manner, even once, will damage the connector
making it unusable.