4
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
DOWNSTREAM CONTROL PRESSURE
B2626
Figure 3. Types Y690AH and Y690AHM Actuator Casing Drainage Schematic
HORIZONTAL PIPELINE
DOWNSTREAM CONTROL LINE
VENT POINTED DOWN
TYPE Y690AHM
VENT POINTED DOWN
HORIZONTAL PIPELINE
TYPE Y690AH
Installation
Y690A Series regulators may be installed in any orientation
as long as ow through the body matches the direction of
the arrow cast on the body. Normal installation is with the
spring case barrel vertical above or below the diaphragm
case. However, when using a Type Y690A or Y690AM
regulator, for proper operation to achieve the published
capacities, the spring case barrel should be installed pointed
down. For actuator casing drainage of the Types Y690AH
and Y690AHM, regulators should be installed as shown in
Figure 3. When exposed to the weather, the spring case
vent should be pointed downward to allow condensate to
drain. On indoor installations, the vent should be piped
outdoors if used in hazardous gas service. External
dimensions and connections are shown in Figure 4.
Capacity Information
Tables 6 and 7 give the regulating capacities of the
Y690A Series regulators at selected inlet pressures and
outlet pressure settings. Flows are in SCFH (60°F and
14.7 psia) of 0.6 specic gravity natural gas. For gases
of other specic gravities, divide the given capacity by
the square root of the appropriate specic gravity of the
gas required. Then, if capacity is desired in normal cubic
meters per hour at 0°C and 1.01325 bar, multiply SCFH by
0.0268. To determine wide-open ow capacities for relief
sizing, use the following formula:
Q =
520
GT
C
g
P
1
Sin
3417
C
1
P
P
1
Deg
where,
C
g
= gas sizing coefcient from Table 2
C
1
= C
g
/ C
v
, or 35 from Table 2
G = gas specic gravity (air = 1.0)
P
1abs
= inlet pressure, psia (add 14.7 psi to gauge inlet
pressure to obtain absolute inlet pressure)
Q = ow rate, SCFH
T = absolute temperature in °Rankine of gas at inlet
Table 5. Outlet Pressures and Spring Part Numbers
TYPES
OUTLET CONTROL
PRESSURE RANGES
SPRING PART
NUMBER
SPRING
COLOR
SPRING WIRE
DIAMETER
SPRING FREE
LENGTH
Inches mm Inches mm
Y690A and Y690AM
1 to 2.5-inches w.c. / 2 to 6 mbar
2.5 to 7-inches w.c. / 6 to 17 mbar
1B558527052
(1)(2)
1B653827052
(1)
Orange
Red
0.072
0.085
1.8
2.2
3.78
3.63
96.0
92.2
Y690AH and Y690AHM
5 to 10-inches w.c. / 12 to 25 mbar
7 to 16-inches w.c. / 17 to 40 mbar
15-inches w.c. to 1.2 psig / 37 to 83 mbar
1B653827052
1B653927022
1B537027052
Red
Unpainted
Yellow
0.085
0.105
0.114
2.2
2.7
2.9
3.63
3.75
4.31
92.2
95.2
109
1.2 to 2.5 psig / 83 to 172 mbar
2.5 to 4.5 psig / 0.17 to 0.31 bar
4.5 to 7 psig / 0.31 to 0.48 bar
1B537127022
1B537227022
1B537327052
Light green
Light blue
Black
0.156
0.187
0.218
4.0
4.8
5.5
4.06
3.94
3.98
103
100
101
1. To achieve the published outlet pressure range the spring case must be installed pointing down.
2. Do not use Fluorocarbon (FKM) diaphragm with this spring at diaphragm temperatures lower than 60°F / 16°C.