Precision Cooling
For Business-Critical Continuity™
Liebert
®
iCOM
User Manual - Intelligent Communications & Monitoring
Vedere la pagina 0
1 2 3 4 5 6 ... 83 84

Sommario

Pagina 1 - Precision Cooling

Precision CoolingFor Business-Critical Continuity™Liebert® iCOM™User Manual - Intelligent Communications & Monitoring

Pagina 2 -

Liebert iCOM Display Components and Functions4Figure 3 Status menu, large display, graphical viewFigure 4 Liebert iCOM default screen symbolsEvaporato

Pagina 3 - TABLE OF CONTENTS

Liebert iCOM Display Components and Functions52.1 Navigating Through the Liebert iCOM MenusLiebert iCOM shows icons and text for monitoring and contro

Pagina 4 - ® . . . . . . . . . . . 48

Liebert iCOM Display Components and Functions62.1.3 Entering a PasswordTo change the value of a parameter in a menu, you must first enter the password

Pagina 5

Liebert iCOM Display Components and Functions7Figure 6 Menu tree—Large display, stand-aloneStatus Menu – System ViewStatus MenuUnit 1 ViewUser MenuUni

Pagina 6

Liebert iCOM Display Components and Functions82.1.4 Viewing Multiple Units with a Networked Large DisplayWhen you first wake up the control, press the

Pagina 7 - 1.0 INTRODUCTION

Liebert iCOM Display Components and Functions9Figure 8 User menu iconsTable 2 User menu iconsIcon NameDescriptionAvailable On DisplaySetpointsView and

Pagina 8

Liebert iCOM Display Components and Functions10Sleep ModeAllows setback settings for non-peak operationSmall & LargeService Contact InfoContains k

Pagina 9

Liebert iCOM Display Components and Functions11Figure 9 Service menu iconsTable 3 Service menu iconsIcon NameDescriptionAvailable OnDisplaySetpoints T

Pagina 10

Operation123.0 OPERATIONThe Liebert iCOM display for your Liebert cooling unit features an easy-to-use, menu-driven liquid crystal display (LCD). All

Pagina 11 - 2.1.2 Accessing Submenus

Operation13AutorestartWhen there is a loss of power to the cooling unit and power comes back, the unit will return to its pre-vious operating status—o

Pagina 13

Operation143.1.3 General Compressor RequirementsLow-Pressure Time DelayWhen the compressor starts, the low-pressure input is ignored for a selected pe

Pagina 14

Operation15Digital Scroll High TemperatureA protective maximum operating compressor temperature limit is imposed on units with digital scroll compress

Pagina 15 - Table 2 User menu icons

Operation163.2 Motorized Ball Valve in Digital Scroll UnitsOn digital scroll units, discharge pressure is controlled by a motorized ball valve. During

Pagina 16

Operation173.3 Temperature Control—Single Source Cooling (No Extra Cooling Coil)3.3.1 Temperature Proportional Band The control uses the temperature p

Pagina 17 - Table 3 Service menu icons

Operation183.3.2 Compressor ControlDepending on the type of Liebert air conditioning unit you have your unit may contain one or two compressors with o

Pagina 18 - 3.0 OPERATION

Operation19Two Compressors With Unloaders—Four-StepThe first two-step compressor is started unloaded at 33% calculated output from the temperature pro

Pagina 19 - Operation

Operation20Digital Scroll CompressorsA compressor with a suction cutoff unloader can only modulate its capacity between two distinct lev-els: fully lo

Pagina 20 - High Pressure Alarm

Operation213.3.3 Chilled Water ControlThe chilled water control valve is adjusted proportionally as the temperature control varies the requirement for

Pagina 21 - 3.1.5 Compressor Sequencing

Operation22The Value setting is the factory default setting on free-cooling and dual cooling units. If the tempera-ture difference between the second

Pagina 22

Operation23GLYCOOL™ Cooling—Free-CoolingWhen GLYCOOL cooling is available, the temperature control will calculate a total cooling require-ment of 200%

Pagina 23

iTABLE OF CONTENTS1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 24 - Compressor Proportional Bands

Operation24Figure 19 Three-stage heating0%Heating65 70Heat 3On½ Dead-band66 67 68 69Heat 2OnHeat 1OnHeat 3OffHeat 2OffHeat 1Off-100 %Heating½ Proporti

Pagina 25

Operation253.5.2 SCR ReheatSCR reheat is a type of electric reheat that provides tighter temperature control than staged electric reheat. SCR reheat c

Pagina 26

Operation26Standard ModeIn Standard mode, the SCR reheat operates only when the Temperature Proportional Band calls for heating. SCR reheat output is

Pagina 27 - 3.3.3 Chilled Water Control

Operation273.6 Humidity ControlThe control uses the humidity proportional band to determine which operation to perform (dehumidi-fication/humidificati

Pagina 28

Operation283.6.1 HumidificationInfrared HumidifierThere are two types of infrared humidifiers: small pan (IFS) and large pan (IFL). The operating mode

Pagina 29 - Dual Cooling Source

Operation293.6.2 DehumidificationThe Dehumidification Enable parameter (Service Menu, Options Setup) allows for enabling/disabling the dehumidificatio

Pagina 30 - Figure 19 Three-stage heating

Operation30Reheat During DehumidificationHot gas reheat or hot water reheat will start as described in 3.5 - Temperature Control—Reheat, when the temp

Pagina 31 - 3.5.2 SCR Reheat

Operation31Intelligent – If Intelligent Control is selected, the return air temperature/humidity is controlled at or near the setpoint. The percent te

Pagina 32

Operation323.7.3 Supply Limit—OptionalChilled water units may be ordered with an additional sensor for monitoring the supply air tempera-ture. This se

Pagina 33 - 3.6 Humidity Control

Operation333.7.5 User Inputs / Customer InputsThe user can connect and specify up to four inputs depending on unit configuration. The user inputs/cust

Pagina 34 - Infrared Humidifier

ii3.9 Next Maintenance Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373.9.1 Calculatio

Pagina 35 - Dehumidification Low Limit

Operation343.7.6 Event Types and PropertiesLiebert iCOM events are used to inform the user of cooling unit operational status. All events are recorded

Pagina 36 - 3.7 Control Types

Operation35Table 8 Possible event settings—some events not available in all unitsEventInternal Delay(Before Action Occurs)Default Delay / Selectable(B

Pagina 37

Operation363.8 POSSIBLE EVENT NOTIFICATIONSTable 9 lists alarms and warnings that may occur in a cooling unit. When any of these occur, they will appe

Pagina 38 - 3.7.3 Supply Limit—Optional

Operation373.9 Next Maintenance CalculationThe next maintenance calculation, as well as the included diagnostics feature, will help run the cool-ing u

Pagina 39

Operation38Parameters for Next Maintenance CalculationGeneral Maintenance Settings• Maintenance Frequency—can be set as one to 12 months or to zero, w

Pagina 40

Teamwork394.0 TEAMWORKUnit-2-Unit (U2U) Communications via a private network will allow the following functions to be placed into operation when the r

Pagina 41

Teamwork40The number of available units is calculated like:• In non-standby configuration: all units with fan on• In typical standby function (no casc

Pagina 42 - OSSIBLE EVENT NOTIFICATIONS

Teamwork414.1.4 Teamwork Mode 2Teamwork Mode 2 is designed to prevent units within a group from working against each other or “fighting.” It is best a

Pagina 43 - Calculating Unit Wellness

Installing a Liebert iCOM Unit-to-Unit Network425.0 INSTALLING A LIEBERT ICOM UNIT-TO-UNIT NETWORKConnecting multiple Liebert iCOM-controlled cooling

Pagina 44

Installing a Liebert iCOM Unit-to-Unit Network435.3 Wiring for Unit-to-Unit Communications—U2UCooling units come from the factory-wired for stand-alon

Pagina 45 - 4.0 TEAMWORK

iiiFIGURESFigure 1 Liebert iCOM components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 46 - Teamwork

Installing a Liebert iCOM Unit-to-Unit Network445.3.1 Wiring a Liebert iCOM U2U NetworkSmall DisplaysTwo cooling units, each with a small display: To

Pagina 47 - Standby and Cascade

Installing a Liebert iCOM Unit-to-Unit Network45Figure 25 Wiring a small display for stand-alone operationFigure 26 Wiring a small display for U2U net

Pagina 48

Installing a Liebert iCOM Unit-to-Unit Network46Figure 27 Wiring a large display for stand-alone operationFigure 28 Wiring a large display for U2U net

Pagina 49

Installing a Liebert iCOM Unit-to-Unit Network47Figure 29 Liebert iCOM input-output control boardLiebert vNSAThe Liebert vNSA is designed to connect m

Pagina 50 - Wall-Mount Large Display

Installing a Liebert iCOM Unit-to-Unit Network48Figure 30 Liebert vNSA with optional remote large display5.4 External Communications—Building Manageme

Pagina 51 - Unit Electronics Compartment

Mounting a Large Display on a Wall496.0 MOUNTING A LARGE DISPLAY ON A WALL6.0.1 Location ConsiderationsConsider these factors before beginning work on

Pagina 52 - U2U CAN CAN

Mounting a Large Display on a Wall50Figure 31 Liebert iCOM display dimensionsRev. 01.92" (49mm) 4.17"(106mm)4.13"(105mm)PrimaryMounting

Pagina 53 - Liebert vNSA

User Menu Parameters517.0 USER MENU PARAMETERSUser menus report general cooling unit operations and status. The password for the user menu is 1490.The

Pagina 54

User Menu Parameters52Table 16 Set alarms parametersFunctionRead/WriteRangeImperial (metric)Large Display Small DisplayPage 1 of 1Password PASSWORD W

Pagina 55 - Mounting Instructions

User Menu Parameters53Active AlarmsPermits viewing all current, active alarms.Daily Low Humidity Lo Humi R 20-80%Daily Low HumidityLo Hu HLo Hu MLo Hu

Pagina 56 - BACK VIEW

ivTABLESTable 1 Keyboard icons and functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 57 - SER MENU PARAMETERS

User Menu Parameters54Table 20 Total run hours parametersFunctionRead/WriteRangeImperial (metric)Large Display Small DisplayPage 1 of 1Actual Hours /

Pagina 58 - Page 1 of 2

User Menu Parameters55Timer Mode Type TIME TYP W System Off, DeadBandDead Band DEADBAND W 4-27°F (2-15°C)Table 22 Service contacts parametersFunctionR

Pagina 59 - Active Alarms

Service Menu Parameters568.0 SERVICE MENU PARAMETERSService menus allow customized settings for site operations. The password for service menu parame-

Pagina 60

Service Menu Parameters57Unit Diary—Large Display OnlyShows all entered program changes and maintenance performed on the unit.VSD Setpoint VSD SET W 0

Pagina 61

Service Menu Parameters58See 3.9.1 - Calculation of Next Maintenance and Diagnostics for details on these menus.Table 25 Standby settings / lead-lag p

Pagina 62 - 8.0 SERVICE MENU PARAMETERS

Service Menu Parameters59Compressor1 Settings (Page 3 of 8)Password PASSWORD W -Number of Starts STARTS W 0-32000Run Hours RUN HRS W 0-32000Average Ru

Pagina 63 - Unit Diary—Large Display Only

Service Menu Parameters60El. Heater 2 Settings (Page 6 of 8) WELLNESS HEAT2Password PASSWORD W -Number of Starts STARTS W 0-32000Run Hours RUN HRS W 0

Pagina 64 - WELLNESS

Service Menu Parameters61Table 27 Diagnostics / service mode parametersFunctionRead/WriteRangeImperial (metric)Large Display Small DisplayPage 1 of 7P

Pagina 65

Service Menu Parameters62Password PASSWORD W -Alarm Relay ALM REL W Off, OnFC Relay FC REL W Off, On3P Actuator Open 3P OPEN W Off, On3P Actuator Clos

Pagina 66

Service Menu Parameters63Page 7of 7Status Humidifier Problem HUM PROB R OK, ActStatus DT1 (Outdoor/Glycol) DT1 R OK, ActStatus DT2 (Glycol/Room) DT2 R

Pagina 67

Introduction11.0 INTRODUCTIONThe Liebert iCOM™ control offers the highest capabilities in unit control, communication and moni-toring of Liebert missi

Pagina 68

Service Menu Parameters64Page 2 of 7Password PASSWORD W -Customer Input 1CUST IN1 W SmokeWater AlarmC PMP AlarmFlow AlarmStdby G PmpStdby UnitC-Input

Pagina 69

Service Menu Parameters65HIGH TEMP SENSOR A HTA W 0 - 9999 secLOW TEMP SENSOR A LTA W 0 - 9999 secHIGH HUM SENSOR A HHA W 0 - 9999 secLOW HUM SENSOR A

Pagina 70

Service Menu Parameters66ENABLE - DISAB - - -COMP 1 OVERLOAD OL1 W Disabled, EnabledCOMP 2 OVERLOAD OL2 W Disabled, EnabledCOMP 1 HIGH PRESSURE HP1 W

Pagina 71 - Page 4 of 7

Service Menu Parameters67COND PUMP-HIGH WATER CPH W Disabled, EnabledLOSS OF FLOW LOF W Disabled, EnabledSTBY GLYCOL PUMP ON SGP W Disabled, EnabledST

Pagina 72

Service Menu Parameters68REHEAT LOCKOUT RL W Disabled, EnabledHUMIDIFIER LOCKOUT HL W Disabled, EnabledFC LOCKOUT FCL W Disabled, EnabledCOMPRESSOR(S)

Pagina 73

Service Menu Parameters69TYPE -- -COMP 1 SHORT CYCLE SC1 W MSG, WRN, ALMCOMP 2 SHORT CYCLE SC2 W MSG, WRN, ALMNO POWER NOP W MSG, WRN, ALMCONDENSER 1

Pagina 74

Service Menu Parameters70Freecool Sensor PTC or NTC FC SNSR W PTC, NTCFreecool Sensor FC SNSR W ±18°F (±9.9°C)Calibrated Freecool Sensor CAL FC R 4-11

Pagina 75

Service Menu Parameters71Netmask — W Netmask RangeGateway — W Gateway RangeMAC — R MAC RangeU2U Protocol — W GBPU2U Address — W 33-64U2U Group — W 1-9

Pagina 76

Service Menu Parameters72Netmask W Netmask RangeGateway W Gateway RangeMAC R MAC RangeU2U Protocol W GBPU2U Address W 1-32U2U Group W 1-99Bootloader V

Pagina 77

Service Menu Parameters73Table 32 Options setup parametersFunctionRead/WriteRangeImperial (metric)Large Display Small DisplayPage 1 of 3Password PASSW

Pagina 78

Liebert iCOM Display Components and Functions22.0 LIEBERT ICOM DISPLAY COMPONENTS AND FUNCTIONSThe small and the large display have a common key layou

Pagina 79 - BALL OFF W

Service Menu Parameters74Table 33 Service contact info parametersFunctionRead/WriteRangeImperial (metric)Large Display Small DisplayPage 1 of 1Passwor

Pagina 80

Service Menu Parameters75Notes

Pagina 81 - Service Menu Parameters

Service Menu Parameters76

Pagina 83

Ensuring The High AvailabilityOf Mission-Critical Data And Applications.Emerson Network Power, the global leader in enabling business-criticalcontinui

Pagina 84 - SL-18835_REV02_10-08

Liebert iCOM Display Components and Functions3Table 1 Keyboard icons and functionsIcon Key Name FunctionOn/Off Key Controls the operational state of t