114.....Avocent® Universal Management Gateway Appliance Installer/User Guide
4. Select the outlets you want to configure and click Edit. You can change the Post On Delay and
Post Off Delay as well as the High Critical, High Warning, Current Low Warning and Low
Critical thresholds.
5. Click Apply when finished.
To configure PDUsettings:
1. Select a PDU to manage.
2. Click on the Settings tab.
3. Click PDU.
4. Select the PDUs you want to configure and click Edit. You can configure Cold Start Delay as
well as High Critical, High Warning, Low Warning and Low Critical thresholds and Estimated
Power Factor.
5. Click Apply when finished.
To configure Phases settings:
1. Select a PDU to manage.
2. Click on the Settings tab.
3. Click Phases.
4. Select the phases you want to configure and click Edit. You can configure High Critical, High
Warning, Low Warning and Low Critical thresholds.
5. Click Apply when finished.
To configure Circuits settings:
1. Select a PDU to manage.
2. Click on the Settings tab.
3. Click Circuits.
4. Select the circuits you want to configure and click Edit. You can configure High Critical, High
Warning, Low Warning and Low Critical thresholds.
5. Click Apply when finished.
To configure Environment settings:
1. Select a PDU to manage.
2. Click on the Settings tab.
3. Click Environment.
Vedere la pagina 119