Emerson EZH and EZHSO Series Pressure Reducing Regulators Manuale delle Istruzioni Pagina 16

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 36
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 15
Europe,
Middle
East,
and
Africa
Document
Only
Types EZH and EZHSO
16
For a single regulator, set the pilot to the desired outlet
(control) pressure according to the Pilot Adjustment procedure.
For a wide-open downstream monitor installation, adjust
the upstream working pilot until intermediate pressure is
higher than the desired setpoint of the monitor pilot. Adjust
the downstream monitoring pilot to the desired monitoring
takeover pressure. Reduce the upstream pilot to the normal
outlet pressure setting.
For a wide-open upstream monitor installation, adjust
the downstream working pilot to a setpoint higher than
the setpoint of the monitor pilot. Adjust the upstream
monitoring pilot to the desired monitoring takeover
pressure. Reduce the downstream pilot to the normal
outlet pressure setting.
For a working monitor installation, adjust the setpoint
of the upstream monitor pilot to the desired maximum
pressure. Adjust the upstream working pilot to the desired
intermediate pressure setting. Adjust the downstream
pilot to a pressure setting slightly above the upstream
monitor pilot pressure setting. Adjust the upstream
monitor pilot to its desired setpoint. Establish nal desired
downstream pressure by adjusting the downstream working
regulator pilot.
10. After adjusting the Type PRX pilot(s) to the desired
pressure setting(s), slowly open the downstream block
valve wide open.
11. Close the bypass valve, if used.
Type OS2 Manometric Box Set Point
Verication Procedure
Using the vent valve supply a pressure equal to the set
pressure foreseen for the regulator.
- 1
st
release relay stage
à Set (Stage 1)
- Slam-shut valve plug
à Open (Stages 2 and 3)
à Progressively increase the pressure until tripping occurs
à Adjust setting if necessary (NTAOS2). Note the
set point value on the equipment or mark it on a
commissioning document
STAGES 2 AND 3
TRIGGERED POSITION
STAGE 1
R121
Figure 15. Setpoint Verication Phase
Type PRX Pilot Adjustment
To adjust a standard Type PRX pilot, loosen the locknut, and
turn the adjusting screw.
Turning the adjusting screw clockwise into the spring case
increases the spring compression and pressure setting.
Turning the adjusting screw counter clockwise decreases the
spring compression and pressure setting
When the required pressure setting is maintained for several
minutes, tighten the locknut to lock the adjusting screw
in position.
Type PRX Pilot Restrictor and Damper
Screw Adjustment
Note
Recommended initial setting of the restrictor
screw is turned completely in (clockwise)
and then turned out 1/2 turn. The damper
screw initial setting is turned completely out
(counter clockwise).
The Type PRX/125 (upstream monitor pilot in
working monitor installations) does not have
a restrictor screw.
The restrictor screw of the Type PRX pilot can be used if there
is hunting of the set pressure. Slowly turning out the restrictor
screw (counterclockwise) will help steady the set pressure.
Turning out the restrictor screw will slightly decrease set
pressure, so adjustment of the pilot adjusting screw may
be necessary.
The damper screw can be turned in (clockwise) to slow the
response of the regulator. It is advisable that adjustment of
the damper and restrictor screws be limited to 1/4 turn at a
time to observe the response of the regulator(s).
SHUTDOWN
CAUTION
If the pilot bleed control line pressure is shut
down rst, the downstream system may be
subjected to full inlet pressure (Pu).
1. If the pilot setting must be disturbed, be sure to keep
some tension on the spring. This will prevent trapping
inlet pressure during blow down.
2. Slowly close the valves in the following order:
- Inlet block valve,
- Outlet block valve,
- Control line valve(s), if used.
3. Open the vent valves to depressurize the system.
Vedere la pagina 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 35 36

Commenti su questo manuale

Nessun commento