Emerson Transient Detection System Specifiche

Navigare online o scaricare Specifiche per Moduli di memoria Emerson Transient Detection System. Emerson Transient Detection System Specifications Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 1
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 0
Features
8GB / 1000+ Events
Technical Specifications
Voltage Phase A, B, & C
Accuracy ± 1%
Range 0-600V
Average, Unbalance, Crest Factor Standard Power Quality – Ability to monitor
voltage at every connected panel
and track system anomalies such as
transients, surges, swells and VTHDs.
Frequency Standard
Accuracy ± 1%
Range 45-67 Hz
VTHD Line-to-Neutral, Line-to-Line
Range 60-850Hz Real Time Measurements – Allows
over 1000 events/reports to be
stored for future analysis
Harmonics Line-to-Neutral, Line-to-Line
Range Fundamental – 13th
RMS ± 1%
SPD Health Status Percent Remaining Event Logging – User configurable
alarm thresholds, time/date stamp,
duration and magnitude of events.
I/O Standard
Relay Outputs Single Relay; x2 Form C sets ( NO, COM, NC)
RJ-45 Port Ethernet
Terminals (#24-#14) RS-485 Communication Communications – Information
easily accessed through the Ethernet
or MODBUS TCP/RTU
communications systems
Events Power Quality & System
Event Logging
SSSllPhL/OtOlt
Advanced Transient Detection System
Surge Protection that Monitors, Measures, and Manages
Emerson Network Power Surge Protection makes it easy to monitor your electrical system by
integrating its advanced Transient Detection Systemand monitoring package within its SPDs. The
web-based device allows the end-user real time power quality measurements, logged events,
statistical summaries and premium power protection. Understanding the severity, type and timing
of the event allows you to analyze trends and ultimately better manage your electrical system.
Standard - All events
Standard
communications
systems
S
u
rge
,
Sag
,
S
w
ell
,
Phase
Loss/O
u
tage
,
O
v
er
v
oltage
,
Temporary Overvoltage (TOV), Voltage
Interruption/Dropout, Neutral Bond, Voltage Harmonics
(VTHD), Over/Under Frequency, Protection Failure
Standard
Embedded Web Page - Convenient
access to present and past data right
at the device.
Date
/
Time Stam
p
with Duration
/
Ma
g
nitude
Sur
g
e Counter, Sa
g
Counter, Swell Counter, w
/
reset
Display LCD 128x64 System Analysis – Manage power
system with statistical summaries
and reporting software.
Communications RS-485, MODBUS TCP/RTU,
Ethernet, SNMP, SMTP, Form C
Embedded Webpage Standard
LCD Display – with capacitive touch
buttons for navigation.
Embedded Webpage
Emerson Network Power Contact information www.EmersonNetworkPower.com/Surge
Surge Protection
100 Emerson Parkway
Binghamton, NY 13905
T: (607) 721-8840
T: (800) 288-6169
F: (607) 722-8713
Emerson Network Power, the Emerson Network Power logo and Edco are trademarks
and service marks of Emerson Electric Co. ©2014 Emerson Electric Co.
While every precaution has been taken to ensure accuracy and completeness herein, Emerson Network Power Surge Protection assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any
errors or omissions. Specifications are subject to change without notice.
Real-Time Monitoring of
Voltages, Event Counts
and SPD Health Status
Power Quality Events
Measured and Recorded
in Detail
Manage Your System with User
Configurable Thresholds and
Power Quality Reporting
TS-70109 Rev. 1/15
Vedere la pagina 0
1

Sommario

Pagina 1 - Embedded Webpage

Features 8GB / 1000+ EventsTechnical SpecificationsVoltage Phase A, B, & CAccuracy ± 1% Range 0-600V Average, Unbalance, Crest Factor Stan

Commenti su questo manuale