www.Fisher.comHARTr Field Device SpecificationFisherr FIELDVUE™ DVC6200 SIS Digital ValveControllerHART Revision Device Type Device Revision Firmware
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201410Command 15: Read Primary Variable Output InformationThis comm
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201411Command 17: Write MessageThis command allows you to write a 2
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201412Command 48: Read Additional StatusThis command was significan
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201413Additional Device StatusCommand 48 returns 9 bytes of data, w
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201414Additional Device Status (continued)Byte Bit Name of Status B
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201415Additional Device Status (continued)Byte Bit Name of Status B
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201416CommonPractice CommandsThe DVC6200 SIS field device supports
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201417Command 33: Read Device VariablesThis command is used to rea
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201418Command 35: Write Primary Variable Range ValuesIn the DVC620
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201419Command 42: Perform Master ResetThis reset command has two op
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 20142IntroductionProduct OverviewThe FIELDVUE DVC6200 SIS digital v
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201420Command 50: Read Dynamic Variable AssignmentsThis command ret
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201421Command 52: Set Device Variable ZeroThis command is used to f
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201422Command 54: Read Device Variable InformationThis command is u
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201423Annex A Compatibility ChecklistManufacturer, Model, and Revis
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201424Annex B DVC6200 SIS Parameters as part of a Rosemount 1410 /1
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201425The FIELDVUE instrument is defined on the Gateway by “Tag” (r
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201426Published Data, used for the Gateway’s OPC and Modbus outputs
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201427Any of these choices [Dynamic Variable, Device Variable ID, o
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201428Each of these status bytes represent eight individual bits wi
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201429ADDITIONAL_STATUS_2 According to Command 48: As defined in th
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 20143Reference DocumentationHART Smart Communications Protocol Spec
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201430ADDITIONAL_STATUS_6 According to Command 48: As defined in th
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201431
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 201432Emerson Process Management Marshalltown, Iowa 50158 USASoroca
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 20144Product InterfacesControl Valve InterfaceThe DVC6200 SIS digit
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 20145Internal Jumpers And SwitchesThe input to the DVC6200 SIS is d
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 20146Dynamic VariablesFour Dynamic Variables are implemented.Defaul
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 20147Unit CodesVariable Units Code Units0 No Units6 Pounds per squa
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 20148Universal CommandsThe DVC6200 SIS field device implements all
Instruction Manual SupplementD103638X012DVC6200 SIS Digital Valve ControllerAugust 20149Command 14: Read Primary Variable Transducer InformationThe tr