The other way is to copy this file in the USB key to download it inside the IPRO (in this
second case it is necessary to use the function block “UPDATE_VISOGRAPH”).
13.6.1 Fine tuning of your project
After the download we can see in our VISOGRAPH that there are some things to modify.
The temperature value is without decimal point:
In the display is showed 265 °C instead of 26.5 °C.
The same problem there is for the SET and BAND.
The images for UP and DOWN page are not necessary in both pages (Stage2).
In the first page is enough the DOWN page.
In the second page is enough the UP page.
The values of SET and BAND are not modifiable.
It is necessary to have the possibility to modify them.
Decimal Point
Open your project and choose the Stage2; select the variable to modify in the page and, in
the” Variables Properties” tab, write the number of decimals in the box “Decimals. In our
case the value will be “1”. This procedure is the same for all the other variables with decimal
point.
If the download is
correct you will find
the following messages.